Tool 01 / NEC 2023 / US wiring

Wire size
calculator

The fastest way to the right wire size, with the maths shown. Enter your load, distance and voltage.

Live

Find your wire gauge

A
V
System
Conductor
Max voltage drop
Wire type
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

How the calculator picks a size

  1. Design current: your load in amps, multiplied by 1.25 if it runs for 3 hours or more (NEC 210.19 and 215.2).
  2. Breaker: the next standard breaker size at or above the design current (NEC 240.6).
  3. Ampacity: the smallest wire whose rating covers that breaker in the right temperature column, after any heat and bundling corrections, and within the small-conductor limits of NEC 240.4(D).
  4. Voltage drop: the smallest wire that keeps drop within your limit over the run, using resistance at 75 C.
  5. Answer: the larger of steps 3 and 4. The result tells you which one decided it.

Full formulas, sources and test cases are on the methodology page.

Wire size by amps

BreakerCopper, 60 C (NM-B)Copper, 75 C (THHN)Aluminum, 75 C
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG8 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A3 AWG4 AWG2 AWG
100 A1 AWG3 AWG1 AWG
125 A-1 AWG2/0 AWG
150 A-1/0 AWG3/0 AWG
200 A-3/0 AWG250 kcmil
Short runs, 30 C ambient, up to three current-carrying conductors. NM-B is not used above 100 A here. Full chart: wire size chart.

Popular gauges

More tools and guides

Wire sizing questions

How do I choose the right wire size?

Find the breaker size for the load (125% of the current for continuous loads), pick the smallest wire whose ampacity covers that breaker in the right temperature column, then check voltage drop over the run. Use whichever size is larger.

What is the 3% voltage drop rule?

The NEC recommends, in informational notes, no more than 3% drop on a branch circuit and 5% total for feeder plus branch circuit. It is a performance guideline, not a mandatory rule, but long runs that ignore it lead to dim lights and motors that run hot.

Why does the calculator default to the 60 C column?

NEC 110.14(C) says circuits of 100 A or less, and conductors from 14 to 1 AWG, use the 60 C ampacity unless the equipment is listed for 75 C. NM-B cable is always held to 60 C. Pick THHN and 75 C terminals if your equipment is rated for it.

Is one-way length or round-trip length used?

Enter the one-way distance from the panel to the load. The calculator doubles it for single-phase and DC circuits, and uses the square root of 3 for three-phase.